SOLAR BOX / EV080 ENGLISH 27 ENGLISH 27 SOLAR BOX / EV080 On the Slave’s configure the following: MAX Set the maximum charging current for the EV connected to this Solar Box. After setting the Slave’s load bal ancing option, there will be an error message on the display: “ERROR NO SERIAL COM”. This indicates, that the Slave unit was not able to communicate to the Master. This message will disappear after the modules are correctly wired up. See also ERROR MESSAGES below. Hardware connections Connect the A, B and GND connections form the Master to the Slave(s). So, A connects to A, B goes to B etc. If you are using the sensorbox, you should also connect the A, B and GND wires to the same screw terminals of the Solar Box. Make sure that the +12V wire coming from the sensorbox is connected to only one Solar Box. This wire will provide power to the sensorbox. ERROR MESSAGES If an error occurs, the Solar Box will stop charging and display one of the following messages: ERROR NO SERIAL COM No signal from the sensorbox or other Solar Box (when load balancing is used) has been received for 10 seconds. Please check the wiring tot the sensorbox or another Solar Box. ERROR NO CURRENT There is not enough current available to start charging, or charging was interrupted because there was not enough current available to keep charging. The Solar Box will try again in 60 seconds. ERROR HIGH TEMP The temperature inside the module has reached 65 o C. Charging is stopped. Once the temperature has dropped to 55 o C charging is started again.