Ratio Electric-Handleiding EV080-3 talen

www.ratio.nl 28 www.ratio.nl TESTING AND CONF IGURING Configure the Solar Box and make sure the option MODE is set to SOLAR. Also make sure the menu option MAINSMET is set to SENSORBOX. After exiting the menu, the measured currents should be visible on the display. From top to bottom the display shows the measured values for L1, L2 and L3. A minus indicates that the power at that phase is delivered to the grid. When using the CT’s, it’s possible that the measured currents are not displayed correctly. If there are negative values shown, while not feeding back to the grid, the voltage input plug (MAINS) on the sensorbox should be reversed. In case of deviating values, check the order of the CT connections on the sensorbox. The value of L1 must be displayed correctly, if the voltage input is also connected to the same phase. If necessary, swapping the CT’s on connection 2 and 3 should be sufficient to get everything right. SPECIF ICATIONS Charging System Cable version car connector Outlet version Power input Power output Earth leakage protection Dimensions Housing Weight Environment Operating Temperature Marking IEC61851, Mode 3 IEC 62196, type 1 or type 2 IEC 62196, type 2 Outlet single-phase or 3 phase, 230V-400V, 16A-32A 3,7 kW, 7,4 kW, 11 kW, 22 kW AC 30mA, DC 6mA 400mm x 250mm x 105mm PC/ABS-VO 4 kg (incl. cable) IP54, rain-tight -25°C to +40°C CE